Products
 
Gensets
Home UPS
 
GENSETS
While power cuts eat into your profits, an inefficient DG set will simply add to your losses. Powered by Powerol engines, Mahindra Powerol DG sets have been designed to ensure you an efficient power supply. This also assures you years of hassle free operations.
 
MAHINDRA POWEROL GENSETS (5-75kVA)
5kVA to 75 kVA – Technical Details
Engine Parameters Unit 5kVA 7.5/10kVA 15kVA 20kVA 25kVA
Engine Model   15LD440 2185 GM 3255 GM 3305 GM 4335 GM
Gross Power – (110%) bhp 9 18 25 30 33
Speed rpm 3000 1500 1500 1500 1500
Cooling System   Air Cooled Water Cooled
Aspiration   Natural Natural Natural Natural Natural
No. of Cylinders   1 2 3 3 4
Displacement cc 442 1365 1895 2048 2527
Governing Class   A2 A1 A1 A1 A1
Starting System 12V DC
Alternator Type Brushless, Single / Three Phase,Class H Insulation
Voltage volts 230 415/230 415/230 415/230 415/230
Speed/Frequency rpm/hertz 3000/50 1500/50 1500/50 1500/50 1500/50
Control Panel AMF / Manual Control Panel - as per specific requirement / application
Fuel Tank Capacity litres Suitable for minimum 12 hours of running
Battery Capacity Ah 35 As per Standard Fitment
Acoustic Enclosure Length mm 1100 2150 2150 2150 2500
Width mm 850 1030 1030 1030 1030
Height mm 895 1250 1239 1239 1400
DG Set Weight kgs. - 800 850 900 950
 
5kVA to 75 kVA – Technical Details
Engine Parameters Unit 25/30kVA 30kVA 35kVA 40kVA
Engine Model   4375 GM 4445 GM 4445TC GM 4575 GM
Gross Power – (110%) bhp 37 44 44 57
Speed rpm 1500 1500 1500 1500
Cooling System   Water Cooled with Radiator
Aspiration   Natural Natural Turbo Turbo
No. of Cylinders   4 4 4 4
Displacement cc 2730 3192 2731 3192
Governing Class   A1 A1 A1 A1
Starting System 12V DC
Alternator Type Brushless, Single / Three Phase,Class H Insulation
Voltage volts 415/230 415/230 415/230 415
Speed/Frequency rpm/hertz 1500/50 1500/50 1500/50 1500/50
Control Panel AMF / Manual Control Panel - as per specific requirement / application
Fuel Tank Capacity litres Suitable for minimum 12 hours of running
Battery Capacity Ah As per Standard Fitment
Acoustic Enclosure Length mm 2500 2500 2500 2500
Width mm 1030 1030 1030 1030
Height mm 1400 1400 1400 1400
DG Set Weight kgs. 1000 1050 1100 1100
 
5kVA to 75 kVA – Technical Details
Engine Parameters Unit 45kVA 50kVA 62.5kVA 75kVA
Engine Model   4575TCI GM 4725 GM 4905 GM 4905 GM
Gross Power – (110%) bhp 57 72 90 90
Speed rpm 1500 1500 1500 1500
Cooling System   Water Cooled with Radiator
Aspiration   Turbo A/C Turbo A/C Turbo A/C Turbo A/C
No. of Cylinders   4 4 4 4
Displacement cc 2731 3192 3532 3532
Governing Class   A1 A1 A1 A1
Starting System 12V DC
Alternator Type Brushless, Single / Three Phase,Class H Insulation
Voltage volts 415 415 415 415
Speed/Frequency rpm/hertz 1500/50 1500/50 1500/50 1500/50
Control Panel AMF / Manual Control Panel - as per specific requirement / application
Fuel Tank Capacity litres Suitable for minimum 12 hours of running
Battery Capacity Ah As per Standard Fitment
Acoustic Enclosure Length mm 2500 2720 3495 3495
Width mm 1030 1030 1150 1150
Height mm 1400 1400 1450 1450
DG Set Weight kgs. 1150 1400 1400 1400
Note: In View of our policy of continuously improving our products, we serve the right to alter specifications or designs
without prior notice and without liability. Illustrations do not necessarily show the product in its standard form.
 
Generates peace of mind
Its recovery time, easily the best in its category, guarantees a seamless switchover to the back-up power. Moreover, its effective governing system controls the voltage fluctuations, thus ensuing complete safety of your equipments.
 
Performance unmatched
Its got one of the most preferred engines fitted inside - the Mahindra Powerol engine. Compact and low on vibration, this engine has the smallest footprint as compared to other engines of identical ratings. Making the DG set apt even for roof-mountings.
 
Silence certified
Each and every Powerol DG set complies with the most stringent noise and emission norms stipulated by the Central Pollution Control Board of India (CPCB).
 
MAHINDRA POWEROL GENSETS (82.5 - 320kVA)
Technical Details
Generator Set Specifications
  82.5/85kVA 100kVA 140kVA 160kVA/180kVA
Engine model 41225 GC 41425 GC 61985 GC 62205 GC
Rated Power (100%), HP (kW) 111 (82) 129 (95) 179 (132) 198 (146)
Overload Power (110%), HP (kW) 122 (90) 142 (105) 198 (146) 219 (161)
Aspiration Turbocharged Turbocharged, After Cooled
Cooling System Liquid Cooled with Radiator
Starting System 24V, Electrical
Governing Class (As per IS 10000) A1, Electronic
No. of Cylinders 4 6 6
Bore x Stroke, mm 114 x 130 114 x 135 114 x 135
Displacement, litres 5.3 8.27 8.27
Compression Ratio 17.3:1 18.1 18.1
Lube Oil Specifications CF4 SAE15W40
Lube Oil Sump Capacity, Litres 15 19 19
Total Coolant capacity, Litres 24.5 26.5 26.2 26.2
Battery Capacity, Ah 150 150 180 180
Length, mm 3210 3605 3805 3905
Width, mm 1210 1210 1600 1600
Height, mm 1785 1785 1985 1985
 
MAHINDRA POWEROL GENSETS (82.5 - 320kVA)
Technical Details
Generator Set Specifications
  200kVA / 225kVA 250kVA 320kVA
Engine model 62805 GC 63455 GC 64205 GC
Rated Power (100%), HP (kW) 253 (186) 312.5 (230) 380.5 (280)
Overload Power (110%), HP (kW) 278 (205) 343.8 (253) 418.5 (308)
Aspiration Turbocharged, After Cooled
Cooling System Liquid Cooled with Radiator
Starting System 24V, Electrical
Governing Class (As per IS 10000) A1, Electronic
No. of Cylinders 6 6 6
Bore x Stroke, mm 114 x 144 135 x 150 135 x 150
Displacement, litres

8.9

12.88 12.88
Compression Ratio 18:1 17.0:1 17.0:1
Lube Oil Specifications CF4 SAE15W40
Lube Oil Sump Capacity, Litres 19 24 24
Total Coolant capacity, Litres 26.2 34.4 34.4
Battery Capacity, Ah 180 180 180
Length, mm 3905 4105 4305
Width, mm 1600 1700 1750
Height, mm 1985 2185 2185
** Rating as per ISO 8528-1:2005 (E), Provision of 10% over loading is applicable as per ISO 8528-1:2005(E)
 
ALTERNATOR SPECIFICATIONS*
Type Brushless, Three Phase
Voltage 415
Rpm/Frequency, Hz 1500/50
Voltage Regulation +1%
Enclosure IP23
Class of Insulation Class H
*Note: for detailed specifications, please refer to the manufacturers leaflet
Note: In view of our policy of continuously improving our products, we reserve the right to alter specifications or designs without prior notice and without liability. Illustrations do no necessarily show the product in its standard form
 
No Compromise technology
It’s got other advantages too. Like, it’s transported through the Mahindra Transport Solutions Group. It is installed and commissioned through a Mahindra authorized dealer. It even comes with an annual maintenance contract. It is most fuel efficient in its class It offers zero-leak engines Manual and AMF control panel options are also available.
 
Preferred by all
A Powerol DG set can be used in the Telecom, Defence and Railway sectors. It can also be installed at places like petrol pumps, hospitals, super markets, banks and construction sites
 
Home UPS
 
We proudly introduce world class Range of Home UPS with 24 months warranty period.

The Home UPS available in following VA
• 600VA
• 800 VA
• 1500 VA
 
LOAD CHART
Rating 600VA 800VA 1500VA
  A B C A B C A B C
Fan 3 2 1 4 3 2 7 6 5
Tube 4 3 3 6 5 3 8 7 6
TV - 1 - - 1 - - 1 -
PC - - 1 - - 1 - - 1
Note : Actual Load Calculations will depend on the manufacturers specification of the above mentioned units
 
Features
• Micro Controller based design
• High Speed, Mostet Protection for excess Current & Voltage Spikes
• Regulated output voltage window during regulated UPS Mode
• The Selectable Battery charging option
• Audio alarms for Mains Failure, Low Battery and Overload
 
Interllicharge Technology
• Two times faster battery charging
• Enhances battery life
• Ensures minimum battery water loss
• Battery charging even at low mains
 
Protection
• Overload with Auto Reset (only in unregulated mode)
• Battery deep discharge protection
• Ultra fast short circuit protection
• Battery reverse polarity